Emicool in Motor City, Dubai (2021)
Power Quality Analysis of chillers and pump units
Efficiency under SCADA Network
Key findings:
- VFD’s, Chillers T/P, Cooling tower pumps and fans, are controlled manually (not PLC-controlled)
- Overall system COP ≤ 3.1
- 30% of temperature sensors defective (inconsistent readings)
- BTU meters reading only the main supply line
- Inconsistent BMS connections to the chillers
- Existing control system (Siemens S7 Industrial PLC) partially out of service
- Critical Power Quality parameters (low PF, high Harmonics, Failing capacitors)
Recommended Improvement Workplan